Filter Fan Plus
FPI/FPO 018 | up to 97 m³/h (124 x 124 mm)

  • New air-flap outlet technology for high airflow
  • Easy mounting
  • Protection type test/Environmental rating by independent testing institutes (VDE & UL)
  • Two systems for optimal airflow (FPI/FPO)
  • Standard enclosure cut-out sizes (5 sizes)
  • One filter mat

Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting airflow prevents formation of localised hot pockets in installations and protects electronic components from overheating.

The Filter Fan Plus series uses a new airflap-outlet technology for the air outlet and thus reaches a high degree of airflow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the application there are two systems that are available - the FPI or FPO system. The FPI system is a standard installation with a filter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airflow direction "In"). This system consists of a filter fan and exit filter. Whereas in the FPO system, the filter fan is located in the upper area of the enclosure to avoid heat buildups (airflow direction "Out"). The FPO system is composed of an intake filter and exit filter fan. The Filter Fan Plus series may also be used outdoors with appropriate protective measures or when equipped with weather proof accessories, e.g. Hose-proof Hood FFH 086.

Axial fan, ball bearingservice life L10 at +40 °C (+104 °F): min. 37,000 h
fan body aluminium, rotor metal
Connection2 stranded wires, 300 mm
Casing, hood, flapsplastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out124 x 124+1 mm
Mounting frame4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter matISO coarse 55 % acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter materialsynthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating/Storage temperature-40 to +70 °C (-40 to +158 °F)
Operating/Storage humiditymax. 90 % RH (non-condensing)
Protection type/Protection class     IP54 / I (earthed)
Environmental rating UL/NEMAUL TYPE 12 / NEMA 12
ApprovalsVDE, UL File No. E234324, EAC
Noteother voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

Airflow direction "In": Filter Fan FPI 018

Art. No.Operating voltageAir volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01871.0-30AC 230 V, 50/60 Hz52 m³/h42 m³/h120 mA19 W49 dB (A)66 mm0.8 kgG3
01871.9-30AC 115 V, 50/60 Hz62 m³/h51 m³/h230 mA18 W53 dB (A)66 mm0.8 kgG3

Airflow direction "In": Exit Filter FPI 118

Art. No.Depth in enclosureWeight (approx.)Air outlet
11871.0-0035 mm0.3 kgair-flap outlet technology

To top

Airflow direction "Out": Filter Fan FPO 018

Art. No.Operating
voltage
Air volume,
free flow
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01881.0-00AC 230 V, 50/60 Hz97 m³/h47 m³/h120 mA19 W49 dB (A)79 mm0.9 kgair-flaps
01881.9-00AC 115 V, 50/60 Hz117 m³/h58 m³/h230 mA18 W52 dB (A)79 mm0.9 kgair-flaps

Airflow direction "Out": Intake Filter FPO 118

Art. No.Depth in enclosureWeight (approx.)Filter mat
11881.0-3022 mm0.2 kgISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %

Filter Mat FM 086

Filter class118 x 118 mmInitial gravimetric arrestance1 packing unit
ISO coarse 55 % acc. to ISO 16890 (G3)Art. No. 08634.0-0057 %5 pieces

To top

Technical Drawings

FPI 018/FPI 118
FPO 018/FPO 118