The compact Smart Sensor CSS 014 electronically records temperature and humidity and converts the measured data into a standardized analog 4-20 mA or a digital IO-Link signal. The converted value signals can be utilized or further processed by a control or monitoring unit, e.g. a PLC control. The Smart Sensor is suitable for installation inside and outside the enclosure, even in harsh environmental conditions as can be found in the wind power industry: in shielded outdoor areas and exposed to vibrations.
Technical Data
Download IO-Link Parameter Leaflet for Smart Sensor with IO-Link Interface
Download IODD for Smart Sensor CSS 014 with IO-Link Interface
Download IODD and all accompanying files, then import IODD file into your control software. Or go to the official IODDfinder by IO-Link.
Measuring signals analog (4-20 mA)/digital (IO-Link) digital (IO-Link) | temperature, humidity events, diagnosis, device data |
---|---|
Load resistance (external) | ≤ 500 Ω (4-20 mA only) |
Connection | M12 round plug connector, IEC 61076-2-101, 4-pin, A-coded, shielded |
Electrical protection | Reverse-polarity, short circuit, overvoltage protection |
Mounting | clip for 35 mm DIN rail, EN 60715 and screw fixing M5 |
Casing | plastic according to UL94 V-0, light grey |
Dimensions | 140 x 40 x 38 mm |
Weight | approx. 50 g |
Fitting position | vertical (connection on top) |
Storage temperature | -40 to +85 °C (-40 to +185 °F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type1/Protection class | IP20 (sensor only IP57) / III (SELV) |
Approvals | VDE, UL File No. E500143 (acc. to IEC 61010-1/DIN EN 61010-1), EAC |
Note | Other measuring ranges on request |
¹ The PCB (printed circuit board) is coated on both sides with a certified protective lacquer to protect against corrosion and for improvement of the tracking resistance.
Art. No. | Interface | Operating voltage | Power consumption max. | Temperature measuring range | Humidity measuring range | Operating temperature |
---|---|---|---|---|---|---|
01420.2-00 | 4-20 mA (analog) | DC 24 V (DC 12-30 V): | 1.8 W (typically 0.4 W) | -40 to +60 °C (-40 to +144 °F) ± 1 K (Max. reaction time t60 195 s) | 0 to 100 % RH ±4%2 (Max. reaction time t60 8 s) | -40 to +70 °C (-40 to +158 °F) |
01411.2-00 | IO-Link (digital, specified acc. to version 1.1) | DC 24 V (DC 18-30 V) | 0.3 W | -40 to +80 °C (-40 to +176 °F) ± 0.3 K3 (Max. reaction time t60 195 s) | 0 to 100% RH ± 3%2 (Max. reaction time t60 14s) | -40 to +80 °C |
2 Tolerance within 20 to 80 % RH / 3 Toleranz within +5 to +60 °C (please request diagram for tolerances outside this range).