- Low surface temperature
- Double insulated (plastic housing)
- Wide voltage range
- Dynamic heating up
- Clip fixing
The heaters are used in enclosures where condensation is to be prevented or the temperature may not fall below a minimum value. In this way corrosion is avoided and an even temperature is ensured. The heaters are designed for permanent operation.
Operating voltage | 120 - 240V AC/DC¹ (min. 110V, max. 265V) |
---|---|
Heating element | PTC resistor - temperature limiting |
Surface temperature | < +85°C (+185°F) (according to VDE 0100), |
except upper protective grille | |
Connection | 2-pole terminal 2.5mm², torque 0.8Nm max. |
Casing | plastic according to UL94 V-0, black |
Dimensions | 98 x 38 x 75mm |
Mounting | clip for 35mm DIN rail, EN 60715 |
Fitting position | vertical airflow (air outlet up, connection on bottom) |
Operating/Storage temperature | -45°C to +70°C (-49°F to +158°F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type/Protection class | IP20 / II (double insulated) |
Approvals | VDE, UL File No. E150057, EAC |
Note | other voltages on request |
¹ Operating with voltages below 140V AC/DC reduces heating performance by approx 10%.
Art. No. | Heating capacity² | Inrush current max. | Recommended pre-fuse T (time-delay) | Weight (approx.) |
---|---|---|---|---|
06040.0-00 | 10W | 1.0A | 2.0A | 0.2kg |
06030.0-00 | 20W | 2.5A | 4.0A | 0.3kg |
06050.0-00 | 30 W | 2,5 A | 4,0 A | 0,3 kg |
² at +20°C (+68°F) ambient temperature
Technical drawing
- www.stego.ru>
- Products>
- Heating>
- Heaters>
- CSK 060 | 10 W to 30 W